Sensors are compatible only with Aranet base stations
Measures: temperature (-40°C to 60°C/ -40°F to 140 °F)
Measures: Relative humidity (0% to 100%)
Line-of-Sight range: up to 3 km/ 1.9mi
Operating environment: indoor and outdoor use
Transmitter power: 14 dBm
Data Transmission: 1, 2, 5, 10 minutes
Battery life: up to 10 years
Protection class: IP42
Dimensions: 115x44x25 mm/ 4.5×1.7×1 in
Aranet T/RH sensor
Measurements | Temperature
Relative Humidity
Line of Sight Range | 3km/1.9mi
Operating environment | Indoor and Outdoor use
Transmitter power | 14 dBm
Frequency | Depends on base station instructions
***Measurement range | Temperature | -40°C to 60°C/-40°F to 140°F
Relative Humidity | 0% to 100%
Temperature measurement accuracy | -10°C to 60°C/14°F to 140°F | 0.4°C/0.72°F
-20°C to -10°C/-4°F to 14°F | 0.6°C/1.08°F
-40°C to -20°C/-40°F to 14°F | 0.9°C/1.62°F
Relative Humidity measurement accuracy | 0 to 80% @ 30°C/86°F | 4%RH
80% to 95% @ 30°C/86°F | 6%RH
Response time Τ63%
** | 4 minutes at 1 m/s airflow
Data Transmission | 1, 2, 5, 10 minutes
Data Protection | Data encryption
Power options | 2 AAA Alkaline batteries (Zn/Mn02)
2 AAA Lithium batteries (Li/FeS2)
Battery life @20°C/68°F | Up to 7 years with Alkaline batteries
Up to 10 years with Lithium batteries
Operating temperature | -20°C to 55°C/-4°F to 131°F with Alkaline batteries
-40°C to 60°C/ -40°F to 140°F with Lithium batteries
Operating humidity | 0% to 100% non-condensing
Dimensions | 115x44x25 mm/ 4.5×1.7×1 in
Weight | 65g/ 2.3oz with Alkaline batteries
57g /2.3ozwith Lithium batteries
Construction | ASA Plastic
Protection class | IP42
**Compatible base stations
** | Aranet PRO, Aranet MINI
Marking | CE, FCC, IC
Included | 2 AAA Alkaline batteries, string
Sensors are made to be placed vertically (with the ventilation opening facing down) thus being resistive to humidity.
- For best accuracy, recommended operating range is 20% to 80% RH (non-condensing) and 5°C to 60°C (41°F to 140°F).
Prolonged operation beyond these ranges may result in a shift of sensor reading, with slow recovery time.
** 1, 2, 5, 10 min interval supported from Aranet PRO v1.3.2 and 2, 5, 10 min from Aranet MINI v3.20.