Operation without cables and wires simplifies the installation. In addition to the ease of reallocation of the devices, it is possible to extend the telemetry network extremely easily: simply attach the new sensor where necessary and configure it from a distance!
Moreover, RHT-Air operates on its own wireless network, without the need to use the company's IT infrastructure, allowing its stand-alone operation.
Highlighted Features
Measurement Range:
Temperature: -40 to 100 °C
Humidity: 0 to 100% RH
- Measurement Accuracy:
Temperature: ±2 °C
RH: ±3 % (20-80 °C) and ±5 % (0-100 °C)
- Measurement Resolution:
Temperature: 0.1 °C (14 bits - 16383 levels)
Humidity: 0.1% (12 bits - 4095 levels)
- Interval between updates: Configurable between 15 seconds and 10 minutes (600 s)
- Response Time:
Temperature: 30 sec (air speed 1 m/s)
Humidity: 8 sec (air speed 1 m/s)
- Display: LCD with 2 indications
- Advanced Functions: Battery Level, Dew Point indication
- Communication Interface: NOVUS Air (IEEE 802.15.4)
- Power Supply: 12-30 Vdc or 3.6 V Lithium Battery (OmniCel , ER14250HD model or EEMB, ER14250M model)
- Estimated battery life: Typical 2 years - 10 minutes update interval @ 25°C
- Dimensions:
Box: 70 x 60 x 35 mm
Probe size: 39 mm
Antenna size: 105 mm
- Operating Conditions: -10 to 70 °C - 0 to 95% RH
- Enclosure: Material Polycarbonate IP40
- USB Configuration: Internal Mini-B type
- Configuration Software: DigiConfig
- Certifications: CE, ANATEL (0172-13-7089), FCC
- Electromagnetic Compatibility: EMC: EN61326-1:2006 CISPR11/EN55011, EN61000-4-2, EN61000-4-3, EN61000-4-4, EN61000-4-6, EN61000-4-8